Waldmann PULSE HFMD version VFC III - with MFT Manual do Utilizador Página 20

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 24
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 19
20
GB Operating Manual Light control “PULSE HFMD - Vers. III“
GB Operating Manual Light control “PULSE HFMD - Vers. III“
Explanation of the functions (part 5)
Function 20
Follow-up time
Function to adjust the time after
which the light is to be switched off
if no presence is detected.
The default setting of the follow-up
time is 10 min.
6 different follow-up times from 5
to 30 min can be set.
The function can be changed on
lights with sensors XXX
/P
Function 30
Presence range
Function to set the detection range
of the presence sensor.
The default setting for the range of
the presence sensor is 80%.
6 different stages from 10% to
100% can be set.
The function can be changed on
lights with sensors XXX
/P
Fig. 3
Key I
Logo
Light
bar
Key II
LED I
LED II
Vista de página 19
1 2 ... 15 16 17 18 19 20 21 22 23 24

Comentários a estes Manuais

Sem comentários